Specifications
|
Cooling capacity | kW | 14,6 | 20,9 | 23,7 | 29,0 | 36,6 | 40,4 | Total power input | kW | 4,8 | 7,1 | 8,6 | 9,8 | 12,1 | 14,0 | ESEER | | 3,43 | 3,25 | 3,11 | 3,27 | 3,38 | 3,19 | Water flow | m³/h | 2,5 | 3,58 | 4,07 | 4,98 | 6,28 | 6,94 | Water pressure drop | kPa | 48,3 | 32,9 | 42,0 | 19,0 | 30,3 | 36,6 | Sound pressure level | dB(A) | 50 | 46 | 47 | 48 | 48 | 55 | Water tank volume | l | 40 | 60 | 60 | 80 | 80 | 80 | Cooling capacity: Outdoor temperature 35°C - chilled water temperature in/out 12/7°C | Sound pressure level calculated according to ISO 3744 at 5 m distance from the unit |
Dimensions
|
L | [mm] | 925 | 925 | 1047 | 1047 | 1060 | 1060 | W | [mm] | 785 | 785 | 913 | 913 | 1405 | 1405 | H | [mm] | 380 | 380 | 465 | 465 | 455 | 455 | | [kg] | 67 | 67.5 | 97 | 97 | 119 | 130 |
L = Length
W = Width H = Height
Prices
Detailed selection / quotation available on request
|